fbpx

FREE STANDARD SHIPPING ON ORDERS $99+

Jackson Systems

Honeywell Y8610U4001 Intermittent Pilot Retrofit Kit

BRAND: Honeywell SKU: Y8610U4001

(1 customer review)

$343.86

MSRP: $824.02
You save 58%

Intermittent Pilot Retrofit Kit

Free Shipping
Ships Tomorrow
Availability:

11 In Stock

Description

The Y8610U is a complete kit for converting conventional standing pilot systems to intermittent pilot systems. It is used on gas-fired atmospheric furnaces, boilers, and heating appliances. Not for use on direct vent, induced draft, or power burner equipment. Meets ANSI Z21.71 standard for automatic intermittent pilot ignition systems on central furnaces and boilers.

Features

  • Use with natural or LP gas
  • Includes gas valve, ignition module, pilot burner hardware, ignition cable, and wiring harness
  • Provides 100 percent pilot gas shutoff if pilot fails to light; after 6-minute delay, trial for ignition is repeated.
  • Ignition trail/delay sequence is repeated until the appliance lights or call for heat is removed.

Additional information

Maximum Valve Load

1A Pilot; 2A Main @ 24 VAC

Pilot Type

Ignitor Electrical Rating

Ignition Type

Pre-Purge

Safety Lockout Timing

Fuel Type

UPC 085267313445

Documents

1 review for Honeywell Y8610U4001 Intermittent Pilot Retrofit Kit

  1. Alfred Rodi (verified owner)

    All as advertised. Fast shipping. Great.

Add a review